HE579DIQ880/881 I/O Module
Brand: HornerHE579DIQ880/881 I/O Module
Brand: HornerSmartBlock I/O is complementary to SmartStix I/O, providing Analog and specialty modules for CsCAN.
SmartBlock is compatible with X-series OCS/RCS Products (XLe, XLt, XL6, NX, QX, RX, RCX) and includes a 5-pin double CsCAN plug and Removable Field Wiring Terminals.
HE579DIQ880
- 8 DC inputs and 8, 5 A relay outputs
HE579DIQ881
- 8 DC inputs and 8, 2.5 A DC outputs
Specifications
Brand
Channels
- 8 DC Input, 8 Relay Output Channels (HE579DIQ880)
- 8 DC Input/Output Channels (HE579DIQ881)
Communication
- SmartStix I/O
Connectors
- 5-Pin CsCan Connector
Display
- Status LEDs
Humidity
- 5 to 95 % - Non-Condensing
Input
- DC Inputs: 12-24 Vdc
Input Impedance
- 10 kiloohms
Isolation
- Contact Isolation to Bus/Ground Power: 1,000 Vac
Lower Threshold
- Current Min. Lower Threshold: 0.3 mA
- Current Min. Lower Threshold: -2.1 mA
- Voltage Min. Lower Threshold: 3 Vdc
Maximum Voltage
- Maximum
Operating Temperature
- 0° to 60° C (32° to 140° F)
Output
- Maximum
Power
- 10-30 Vdc
Power Requirement
- AC InRush: 120 mA for 10 milliseconds
- DC Inrush: 12 A for 50 µs
- Steady State 2 W (80 mA at 24 Vdc)
Response Time
- Network Time Plus 10 milliseconds
Supply Voltage
- Output Supply Voltage (VS): 9-30 Vdc
Upper Threshold
- Current, Max.
- Voltage, Max.
Voltage Drop
- 0.5 V